Ammonia Refrigeration System Pipe Colors and Markings
Overview
International Institute of Ammonia Refrigeration (IIAR) Bulletin No. 114 defines the pipe marking standard for ammonia refrigeration systems, building on the general requirements of ANSI/ASME A13.1.1 Scheme for the Identification of Piping Systems (IIAR Bulletin 114 was previously referred to as bulletin 14).
The exact labeling and color coding of ammonia piping and system components may vary, including changes based on when the system, or portion of a system was installed. Always verify with the ammonia system owner/operator.
Ammonia Specific Pipe Colors (Optional)Current and Legacy)
See Pipe Color CodesCoding Scheme (ASEM A13.1) Page
Older Ammonia Pipe Color Codes Prior to ASME A13.1
- High Pressure Liquid: Orange (Pantone 152C)
- High Pressure Vapor: Yellow (Pantone 109C)
- Low Pressure / High Temp (Liquid & Vapor): Light Blue (Pantone 298C)
- Low Pressure / Low Temp (Liquid & Vapor): Dark Blue (Pantone 3015C)
- Low Pressure / Low-Low Temp (Liquid & Vapor): Purple (Pantone 2617C)
- Relief Vent Piping: Gray
- Water / Glycol: Green
Ammonia Pipe Markers (Labels)
Ammonia pipe markers will contain five sections of information including:
- Abbreviation Section: Printed in black
- Physical State Section: Either LIQUID or VAPOR
Printed in yellow for Liquid and sky blue for Vapor - Marker Body: Body color to be Safety Orange and contain the refrigerant "AMMONIA" printed in black
- Pressure Level Section: Either LOW or HIGH.
Pressure in excess of 70 psig will be considered to be high pressure and printed in black letters on a red band.
Pressure equal to or less than 70 psig will be considered to be low pressure and printed in black on a green band. - Directional Arrow: Detachable arrow printed in black.
PHOTO: Diagram of an ammonia pipe label including the product/contents name, physical state, pressure, pipe abbreviation, low/high pressure destination, and direction of flow arrow. The detailed tempature and pressure may be included as optional information.
Pipe Marker Label Abbreviations
International Institute of Ammonia Refrigeration (IIAR) Bulletin No. 114 includes 31 approved abbreviations for ammonia pipe markers. The table below lists the abbreviations.
Table: List of abbreviations used in IIAR bulletin 114. Copyright ER Playbook.
Ammonia Refrigeration System Components / Equipment
Ammonia refrigeration system vessels and major components should be labeled as follows:
- Background: Safety orange with black lettering.
- Dimensions: Typically 3.5 inches wide by a length proportional to the equipment name.
- Text Size: Equipment names should be feature lettering 2.5 inches high.
- Content: Identifies the specific vessel or component name (e.g., "RECEIVER")
Prior to March 2014, IIAR Bulletin No. 114 recommended SAFETY YELLOW as the background color for component markers.
PHOTO: Diagram of an high pressure ammonia received vessel labeled in accordance with IIAR bulletin 114. Ammonia refrigeration system components or equipment may be painted a non-significant color such as grey or green, or they may be color coded as orange for liquid ammonia or yellow for ammonia vapor. Copyright ER Playbook.
Ammonia System Component/Equipment Abbreviations
Table: List of abbreviations used in IIAR bulletin 114. Copyright ER Playbook.